Wire Voltage Drop Calculator
How to Calculate Voltage Drop
Every wire has resistance, so some voltage is lost along the way to the load. For DC and single-phase AC circuits, voltage drop is:
Voltage drop = 2 × current × one-way length × resistance per foot
The 2 counts the trip out and back. Three-phase circuits use 1.732, the square root of 3, in place of the 2. This calculator uses the NEC's resistance values for stranded wire at 75°C, which is close to how warm wire runs under load.
Enter the one-way distance from the panel or power source to the load, not the total length of wire in the circuit.
Example: a 20 amp circuit to a shed 100 ft away
On 120 volts with 12 AWG copper, the drop is 2 × 20 × 100 × 1.98 ÷ 1,000 = 7.92 volts. That's 6.6%, so the shed gets about 112 volts. Moving up to 10 AWG brings the drop to 4.96 volts, or 4.1%. With 8 AWG it's 3.11 volts, or 2.6%, within the 3% the NEC suggests for a branch circuit.
Longest run that stays within 3%
| Circuit | Copper wire | Longest one-way run |
|---|---|---|
| 15 A at 120 V | 14 AWG | 38 ft |
| 20 A at 120 V | 12 AWG | 45 ft |
| 20 A at 120 V | 10 AWG | 72 ft |
| 30 A at 240 V | 10 AWG | 96 ft |
| 50 A at 240 V | 6 AWG | 146 ft |
These distances assume the circuit carries its full rated current. A circuit that usually carries less current can run farther before it reaches 3%.
How much drop is acceptable?
The National Electrical Code suggests at most 3% on a branch circuit and 5% for the feeder and branch circuit together. These figures are in informational notes, so they're recommendations, not requirements, but many electricians and inspectors use them. Motors, compressors and electronics can run hot or fail early when the voltage is too low.
Voltage drop isn't the only check
A wire with low voltage drop must still be large enough to carry the current safely. That's a separate rule, called ampacity. Use the wire size calculator, which checks both and picks the larger wire. Codes also set rules for loads that run for three hours or more, for conduit fill and for hot locations, which this calculator doesn't cover.
Frequently Asked Questions
What is voltage drop?
Voltage drop is the reduction in voltage that occurs along a wire or cable as electrical current flows through it. This happens because:
- All conductors have some electrical resistance
- This resistance causes some electrical energy to be converted to heat
- The longer the wire or the smaller its diameter, the greater the voltage drop
Why is voltage drop important?
Managing voltage drop is crucial for electrical installations because:
- Excessive voltage drop can cause equipment to malfunction or operate inefficiently
- The NEC suggests keeping drop to 3% on a branch circuit and 5% overall, in informational notes rather than requirements
- Proper wire sizing helps ensure safe and efficient operation
- Reducing voltage drop can improve energy efficiency
How do different wire materials compare?
The two main conductor materials have different characteristics:
- Copper has lower resistance and better conductivity
- Aluminum is lighter and typically less expensive
- Aluminum requires larger gauge wire for the same current capacity
- Both materials are widely used in electrical installations
What's the difference between DC and AC calculations?
DC and AC voltage drop calculations differ in several ways:
- DC calculations consider only resistance
- Single-phase AC includes both conductors in the circuit
- Three-phase AC uses a different multiplier due to phase relationships
- Power factor may affect AC calculations in some cases